Why Ultrasound Can’t Tell the Full Story on Partial Discharge 

Ultrasound is a powerful tool for detecting surface-level faults like arcing, tracking, and corona—but it can’t uncover the full scope of partial discharge. In this RED Talk, Josh Robinson cuts through the half-truths, explains the difference between surface and subsurface PD, and shows which technologies really work where ultrasound cannot.

“One of the big ones that I absolutely hate,” Robinson says, “is when people say that ultrasound can detect partial discharge. It’s not a lie, but it’s not the whole truth in the statement.”

Partial discharge is one of those terms that gets thrown around constantly in maintenance circles, and yet most of the time it’s not being explained properly. In his RED Talk, Ultrasound and Partial Discharge, Josh Robinson doesn’t shy away from calling this out.

“One of the big ones that I absolutely hate,” Robinson says, “is when people say that ultrasound can detect partial discharge. It’s not a lie, but it’s not the whole truth in the statement.” That difference between a half-truth and the reality is where much of the confusion begins.

Robinson makes the distinction clear by splitting partial discharge into two categories: surface faults and subsurface faults. Surface faults are exactly what the name suggests—faults along the surface of equipment. Because they emit an audible signal, they can be identified with ultrasound. “Surface faults are faults that are along the surface and they emit an audible signal that can be detected with ultrasound—arcing, tracking, corona.” For these cases, ultrasound is an effective and reliable inspection method.

But that’s only part of the story. “That is not the full scope of what partial discharge is,” Robinson explains. “Partial discharge can also be subsurface faults. Subsurface faults don’t make sound because they’re below the surface.” He gives the example of a wire with a small void inside its insulation, maybe created during manufacturing or when the cable was pulled in and nicked. Over time, microscopic sparks jump from the conductor to the void, and the damage spreads until the insulation fails. “One day, bang, the gear goes out,” Robinson says. “There is no ultrasound device in the world that is ever going to detect that because it’s not a surface fault.”

If ultrasound can’t pick up subsurface PD, then what can? Robinson points to technologies such as TEV, transient earth voltage sensors, which pick up the electrons escaping from the insulation. He uses a simple analogy to make it clear: “I’ll give the example of a hose because partial discharge is kind of hard to visualize. You got a hose, it’s got a tiny little hole in it, and you turn on that hose. There’s no real pressure in that hose, so you never know there’s a leak in it. And one day you crank the pressure up on that hose and now that tiny little pinhole is spraying water everywhere.” The void inside insulation is the same: undetectable at low stress but catastrophic under higher voltage. “That void in the insulation of a piece of wire is like a pinhole in a hose. If there isn’t enough voltage running through that wire, you’ll never know it was there.”

For voltages under 5 kV, subsurface PD isn’t accepted as being present, but above that threshold, failure becomes a real risk. That’s where inspection methods beyond ultrasound are essential. “The TEV is transient earth voltage is detecting those electrons that are dripping out the wire. Ultrasound doesn’t pick that up.” In gas-insulated switchgear, the challenge is even greater. Because the equipment is insulated with gas, ultrasound can’t detect internal faults. “Gas insulated switch gear is tough to do ultrasound on because it’s insulated with gas. It can still have partial discharge faults. If partial discharge is there, you’d have to use something called a UHF or ultra high frequency transform that you stick on the side of equipment. This block can detect a PD fault inside of a gas insulated switch.” Another tool is the HFCT, or high frequency current transformer. “It’s a little CT clamp that you put over a wire and it tells you if PD is present in that wire. Put it on the ground, it tells you if it’s present somewhere in that system. Again, ultrasound cannot detect that.”

The message, then, is not that ultrasound is useless—far from it. It is a powerful tool for surface-level faults, but pretending it can detect every kind of partial discharge is misleading. “So when manufacturers go in there and they say ultrasound detects PD, they’re not lying. They’re not telling the whole truth. And that makes us all look bad.” For Robinson, accuracy in how these tools are presented is as important as the tools themselves. “I’d like to see people accepting that we’re not talking crap and then the sales guys not talking crap.”

What this really means for maintenance teams is that no single technology can cover the full scope of PD detection. Ultrasound has its place for arcing, tracking, and corona, but TEV, UHF sensors, and HFCT clamps are the methods needed to uncover subsurface issues. By using the right tool for the right fault type, reliability teams can avoid being blindsided by failures that ultrasound alone could never predict.

Robinson doesn’t mince words, and that’s what makes his talk so valuable. Rather than dressing up the message, he cuts through the sales gloss to clarify what’s real and what’s not. As he makes clear, the goal isn’t to diminish ultrasound, but to put it in its proper place. To hear his full take, with all the analogies, examples, and hard truths, watch the video Ultrasound and Partial Discharge, available now on RED Talks.